192334 – Pepperl+Fuchs
STOCK: 0.00 unidade(s)
KFU8-UFT-2.D.FA Frequency Converter 2Channel NAMUR “P+F”
Universal usage at different power supplies
Dry contact or inputs
Input frequency 1 mHz … 1 kHz
Current output 0/4 mA … 20 mA
Relay contact and transistor output
Start-up override
Configurable by PACTware or keypad
Line fault detection (LFD)
Signal type Digital Input
Supply
Connection terminals 23, 24
Rated voltage 20 … 90 V DC / 48 … 253 V AC 50 … 60 Hz
Rated current approx. 130 mA
Power dissipation 2.2 W / 3.5 VA
Power consumption 2.5 W / 4 VA
Interface
Programming interface programming socket
Input
Connection side field side
Connection input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II 2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current 8.2 V / 10 mA
Switching point/switching hysteresis logic 1: > 2.5 mA ; logic 0: < 1.9 mA
Pulse duration min. 250 µs , overlap on direction of rotation signal: = 125 µs
Input frequency rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detection breakage I = 0.15 mA; short-circuit I > 4 mA
Input III, IV
Active/Passive I > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current 18 V / 5 mA
Output
Connection side control side
Connection output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, II signal, relay
Contact loading 250 V AC / 2 A / cos f = 0.7 ; 40 DC / 2 A
Mechanical life 5 x 107 switching cycles
Energized/De-energized delay approx. 20 ms / approx. 20 ms
Output III and IV signal , electronic output, passive
Contact loading 40 V DC
Signal level 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: blocked output (off-state current = 10 µA)
Output V analog
Current range 0 ... 20 mA or 4 ... 20 mA
Open loop voltage max. 24 V DC
Load max. 650 O
Fault signal downscale I = 3.6 mA, upscale I = 21.5 mA (acc. NAMUR NE43)
Programming interface
Connection programming socket
Interface RS 232
Transfer characteristics
Input I and II
Measurement range 0.001 ... 1000 Hz
Resolution slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracy slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring time frequency measurement: < 100 ms
Influence of ambient temperature 0.003 %/K (30 ppm)
Output I, II
Response delay = 200 ms
Output V
Resolution < 10 µA
Accuracy < 30 µA
Influence of ambient temperature 0.005 %/K (50 ppm)
Galvanic isolation
Input I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, III reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/input III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/V basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output V/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output III, IV basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elements LEDs , display
Control elements Control panel
Configuration via operating buttons
via PACTware
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2006
Low voltage
Directive 2014/35/EU EN 61010-1:2010
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass 300 g
Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Classifications
System Classcode
ECLASS 11.0 27210128
ECLASS 10.0.1 27210128
ECLASS 9.0 27210128
ECLASS 8.0 27210190
ECLASS 5.1 27210121
ETIM 8.0 EC002918
ETIM 7.0 EC002918
ETIM 6.0 EC002918
ETIM 5.0 EC002475
UNSPSC 12.1 39121007