Autosimatic - Grupo Luminag

1SDA054023R1 – ABB

1SDA054023R1 – ABB

STOCK: 0.00 unidade(s)
T4S 250 PR221DS-LS/I In=250 3p F F CircuitBreaker TMax “ABB”

Long Description:C.BREAKER TMAX T4S 250 FIXED THREE-POLE WITH FRONT TERMINALS AND SOLID-STATE RELEASE IN AC PR221DS-LS/I R 250
Categories
Products » Low Voltage Products and Systems » Circuit Breakers » Moulded Case Circuit Breakers » Tmax T
Conflict Minerals Reporting Template (CMRT):Document availability on demand
Toxic Substances Control Act – TSCA:9AKK108467A8326
Environmental
Environmental Information:9AKK10103A1057
REACH Declaration:9AKK108466A1425
RoHS Information:9AKK108466A1424
RoHS Status:Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Ordering
E-Number (Finland):3655177
E-Number (Sweden):3180324
EAN:8015644551094
Minimum Order Quantity:1 piece
Customs Tariff Number:85362090
Dimensions
Product Net Width:105 mm
Product Net Height:205 mm
Product Net Depth / Length:103.5 mm
Product Net Weight:3.645 kg
Container Information
Package Level 1 Units:1 piece
Package Level 1 Width:248 mm
Package Level 1 Height:240 mm
Package Level 1 Depth / Length:285 mm
Package Level 1 Gross Weight:3.5 kg
Package Level 1 EAN:8015644551094
Additional Information
Electrical Durability:8000 cycle
120 cycles per hour
Mechanical Durability:20000 cycle
240 cycles per hour
Number of Poles:3
Power Loss:at Rated Operating Conditions per Pole 10.7 W
Product Main Type:SACE Tmax T
Product Name:Moulded Case Circuit Breaker
Product Type:Automatic Circuit Breaker
Rated Current (In):250 A
Rated Impulse Withstand Voltage (Uimp):8 kV
Rated Insulation Voltage (Ui):1000 V
Rated Operational Voltage:690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):(220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 40 kA
(500 V AC) 30 kA
(690 V) 25 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):(220 V AC) 85 kA
(230 V AC) 85 kA
(380 V AC) 50 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 40 kA
(500 V AC) 30 kA
(690 V AC) 25 kA
Rated Uninterrupted Current (Iu):250 A
Release:PR221DS-LS/I
Release Type:EL
Short-Circuit Performance Level:S
Standards:IEC
Sub-type:T4
Suitable For:T4
Suitable for Product Class:Moulded Case Circuit Breakers
Terminal Connection Type:Fixed Circuit-Breakers
Front
Test Voltage Max (Utest):3500 V
Test Voltage at Industrial Frequency for 1 Minute:3500 V
Version:F
Certificates and Declarations
Data Sheet, Technical Information:1SDC210004D0203
Declaration of Conformity – CE:9AKK106713A5540
GL Certificate:1SDL000163R0061
Instructions and Manuals:1SDH000436R0001
Instructions and Manuals (Part 2):ITSCE-RH0100001
Classifications
ETIM 7:EC000228 – Power circuit-breaker for trafo/generator/installation protection
ETIM 8:EC000228 – Power circuit-breaker for trafo/generator/installation protection
Object Classification Code:Q
UNSPSC:39121100
WEEE Category:5. Small Equipment (No External Dimension More Than 50 cm)
eClass:V11.1 : 27370409

REF: 1SDA054023R1 Categoria: