M22-R10K PotentioMeter Classical M22 22.5mm 0.5W “Eaton”

R 10 kOhm, P, Bezel: titanium
RMQ design
Classical
Part group reference (e.g. DIL)
Mounting hole diameter [?]
22.5 mm
Basic function
Potentiometer
Single unit/Complete unit
Single unit
Description
3 individual screw terminals
Accuracy of resistance value: ± 10% (linear)
mechanical angle of rotation: 285° (+0/-5°)
Contact sequence
116S107
Impedance [R]
10 k?
Rated power [P]
0.5 W
Degree of Protection
IP66
Front ring
Bezel: titanium
Connection to SmartWire-DT
no
For use with
DILET…
ETR4-70
TECHNICAL DATA
General
Standards
IEC/EN 60947
VDE 0660
Lifespan, mechanical [Operations]
25000
Climatic proofing
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Degree of Protection
IP66
Ambient temperature
Open
-25 – +70 °C
Mounting position
As required
Mechanical shock resistance
30
Shock duration 11 ms
Sinusoidal
according to IEC 60068-2-27 g
Terminal capacities
Solid
0.5 – 1.5 mm2
Terminal capacities
Stranded
0.5 – 1.5 mm2
Tightening torque for terminal screw
0.5 Nm
shipping classification
DNV
GL
LR
0000SPC-1830000SPC-1800000SPC-179
Contacts
Rated impulse withstand voltage [Uimp]
4000 V AC
Rated insulation voltage [Ui ]
250 V
Overvoltage category/pollution degree
III/3
DESIGN VERIFICATION AS PER IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation [In]
0 A
Heat dissipation per pole, current-dependent [Pvid]
0 W
Equipment heat dissipation, current-dependent [Pvid]
0 W
Static heat dissipation, non-current-dependent [Pvs]
0.5 W
Heat dissipation capacity [Pdiss]
0 W
Operating ambient temperature min.
-25 °C
Operating ambient temperature max.
+70 °C
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard’s requirements.
10.2 Strength of materials and parts
10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2 Strength of materials and parts
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
10.2.7 Inscriptions
Meets the product standard’s requirements.
10.3 Degree of protection of ASSEMBLIES
Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances
Meets the product standard’s requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections
Is the panel builder’s responsibility.
10.8 Connections for external conductors
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.3 Impulse withstand voltage
Is the panel builder’s responsibility.
10.9 Insulation properties
10.9.4 Testing of enclosures made of insulating material
Is the panel builder’s responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility
Is the panel builder’s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
TECHNICAL DATA ETIM 8.0
Low-voltage industrial components (EG000017) / Potentiometer for command devices (EC001027)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Potentiometer for command devices (ecl@ss10.0.1-27-37-12-27 [AKF045014])
Resistance
10000 Ohm
Power consumption
0.5 W
Hole diameter
22.5 mm
Number of revolutions
1 – 1
Type of electric connection
Screw connection
Degree of protection (IP)
IP66
Degree of protection (NEMA)
Other
APPROVALS
Product Standards
IEC/EN 60947-5-1; UL 508; CSA-22.2 No. 14-05; CE marking
UL File No.
E29184
UL Category Control No.
NKCR
CSA File No.
012528
CSA Class No.
3211-03
North America Certification
UL listed, CSA certified
Degree of Protection
IEC: IP 66; UL/CSA Type: 3R, 4X, 12, 13
DIMENSIONS
116X217

REF: 229491 Categoria: