QUINT-PS/24DC/24DC/10 Converter DC/DC “Phoenix Contact”

Primary-switched QUINT DC/DC converter for DIN rail mounting with SFB (Selective Fuse Breaking) Technology, input: 24VDC, output: 24 V DC/10A
QUINT DC/DC converter with maximum functionality
DC/DC converters alter the voltage level, regenerate the voltage at the end of long cables or enable the creation of independent supply systems by means of electrical isolation.
QUINT DC/DC converters magnetically and therefore quickly trip circuit breakers with six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
DC operation
Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 32 V DC
Extended input voltage range in operation 14 V DC … 18 V DC (Derating)
Wide-range input no
Input voltage range DC 18 V DC … 32 V DC
14 V DC … 18 V DC (Consider derating during operation)
Voltage type of supply voltage DC
Inrush current < 15 A (typical) Inrush current integral (I2t) < 2.7 A2s Mains buffering time > 12 ms (24 V DC)
Current consumption 14 A (24 V, IBOOST)
Reverse polarity protection = 30 V DC
Protective circuit Transient surge protection; Varistor
Input fuse 25 A (internal (device protection))
Recommended breaker for input protection 16 A … 20 A (Characteristics B, C, D, K)
Efficiency > 92 %
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C … 60 °C)
POWER BOOST (IBoost) 12.5 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / C2 / C4
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance 35 V DC
Protection against overvoltage at the output (OVP) < 35 V DC Max. capacitive load unlimited Active current limitation Approx. 18 A Control deviation < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Residual ripple < 20 mVPP Output power 240 W Peak switching voltages nominal load < 10 mVPP (20 MHz) Maximum no-load power dissipation 1.6 W Power loss nominal load max. 24 W Rise time < 2 ms (UOUT (10 % ... 90 %)) Connection in parallel yes, for redundancy and increased capacity Connection in series yes 2 (Devices) Signal: DC OK active Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current < 20 mA (short-circuit-proof) Signal: POWER BOOST, active Output description IOUT < IN: High signal Switching voltage range 18 V DC ... 24 V DC Maximum inrush current < 20 mA (short-circuit-proof) Signal: UIN OK, active Output description UIN > 19.2 V: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current = 20 mA (short-circuit-proof)
Signal: DC OK floating
Output description Relay
Output voltage = 30 V AC/DC
Maximum inrush current = 100 mA
Connection method Pluggable screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Output
Connection method Pluggable screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Signal
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Types of signaling LED
Active switching output
Relay contact
Signal output: DC OK active
Status display “DC OK” LED green
Color green
Signal output: POWER BOOST, active
Status display “BOOST” LED yellow/IOUT > IN : LED on
Color yellow
Note on status display LED on
Signal output: UIN OK, active
Status display LED “UIN < 19.2 V" yellow/UIN < 19.2 V DC: LED on Color yellow Note on status display LED on Signal output: DC OK floating Note on status display UOUT > 0.9 x UN: Contact closed
Number of phases 1.00
Insulation voltage input/output 1.5 kV (type test)
1 kV (routine test)
1 kV (type test)
Product type DC/DC converters
MTBF (IEC 61709, SN 29500) > 763000 h (40 °C)
Insulation characteristics
Protection class III
Degree of pollution 2
Width 48 mm
Height 130 mm
Depth 125 mm
Installation dimensions
Installation distance right/left 0 mm / 0 mm (= 70 °C)
Installation distance right/left (active) 15 mm / 15 mm (= 70 °C)
Installation distance top/bottom 50 mm / 50 mm (= 70 °C)
Installation distance top/bottom (active) 50 mm / 50 mm (= 70 °C)
Alternative assembly
Width 122 mm
Height 130 mm
Depth 51 mm
Mounting type DIN rail mounting
Assembly instructions alignable: PN =50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom Mounting position horizontal DIN rail NS 35, EN 60715 With protective coating No Color aluminium Housing material Metal Type of housing Aluminum (AlMg3) Hood version Galvanized sheet steel, free from chrome (VI) Ambient conditions Degree of protection IP20 Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C derating, 2.5 %/K, startup at -40°C type-tested)
Ambient temperature (storage/transport) -40 °C … 85 °C
Ambient temperature (start-up type tested) -40 °C
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) = 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 5 Hz, amplitude ±1.6 mm (according to IEC 60068-2-6) 5 Hz ... 100 Hz, 4g, 90 min. Rail applications EN 50121-4 Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV) Standard - Electrical safety EN 60950-1/VDE 0805 (SELV) Standard – Safety extra-low voltage EN 60950-1 (SELV) EN 60204 (PELV) Standard - Safe isolation DIN VDE 0100-410 Shipbuilding approval DNV GL (EMC B) UL approvals UL/C-UL listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) EMC requirements for noise emission EN 61000-6-3 EN 61000-6-4 EMC requirements for noise immunity EN 61000-6-1 EN 61000-6-2 Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 8 kV (Test Level 4) Discharge in air 15 kV (Test Level 4) Comments Criterion A Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 10 V/m (Test Level 3) Frequency range 1 GHz ... 2 GHz Test field strength 10 V/m (Test Level 3) Frequency range 2 GHz ... 3 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Input 2 kV (Test Level 3 - asymmetrical) Output 2 kV (Test Level 3 - asymmetrical) Signal 2 kV (Test Level 4 - asymmetrical) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 Input 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Output 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 2 - asymmetrical) Comments Criterion A Conducted interference Standards/regulations EN 61000-4-6 Conducted interference I/O/S asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Emitted interference Standards/regulations EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself.