QUINT-ORING/24DC/2X10/1X20 Redundancy “Phoenix Contact”
The Auto Current Balancing ACB technology of the QUINT ORING modules doubles the service life of redundantly operated power supplies by evenly utilizing the power supply units. The load current is automatically distributed symmetrically
Nominal input voltage range 24 V DC
Input voltage range 18 V DC … 28 V DC (SELV)
Input voltage range DC 18 V DC … 28 V DC (SELV)
Voltage type of supply voltage DC
Reverse polarity protection < yes60 V
Nominal input current (IN) 2x 10 A (-25 °C ... 60 °C)
1x 20 A (-25 °C ... 60 °C)
Maximum current Imax 2x 15 A (-25°C ... 40°C)
1x 30 A (-25°C ... 40°C)
60 A (12 ms, SFB Technology)
Transient surge protection Varistor
Voltage drop, input/output 0.1 V (IOUT = 20 A)
Efficiency > 98 %
Nominal output voltage 0.1 V (< DC input)
Output voltage UIn -
Nominal output current (IN) 20 A (Increasing power)
10 A (Redundancy)
Derating 60 °C ... 70 °C (2.5%/K)
Protection against overvoltage at the output (OVP) < 32 V DC
Power loss nominal load max. 2 W (IOUT = 20 A)
Connection in series No
Signal: Redundancy OK, 13/14
Output description Group contact
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current = 100 mA (short-circuit-proof)
Output description Contact closed: ? UIN = 300 mV
Maximum switching voltage max. 30 V AC/DC
Maximum inrush current = 100 mA (short-circuit-proof)
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 8 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 10
Stripping length 7 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Connection method Screw connection
Conductor cross section, rigid min. 0.2 mm²
Conductor cross section, rigid max. 4 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 12
Stripping length 10 mm
Screw thread M3
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Types of signaling Relay contact, floating, current limited
Status display LED redundancy OK
Note on status display green
Color green
Status display ACB OK LED
Note on status display LED bar graph green
Color green
Note on status display LED bar graph green
Insulation voltage input, output / housing 500 V
Product type Redundancy module
Product family QUINT ORING
MTBF (IEC 61709, SN 29500) > 1000000 h (40 °C)
Protection class III
Degree of pollution 2
Width 32 mm
Height 130 mm
Depth 125 mm
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Width 122 mm
Height 130 mm
Depth 35 mm
Mounting type DIN rail mounting
Assembly instructions alignable: PN =50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position horizontal DIN rail NS 35, EN 60715
Flammability rating according to UL 94 (housing / terminal blocks) V0
Housing material Metal
Type of housing Aluminum (AlMg3)
Hood version Galvanized sheet steel, free from chrome (VI)
Housing material Steel sheet, zinc-plated
Degree of protection IP20
Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude 2000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) = 100 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g tv = 90 min.
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations EN 50178/VDE 0160 (PELV)
Standard - Electrical safety EN 60950-1/VDE 0805 (SELV)
Standard – Safety extra-low voltage IEC 60950-1 (SELV) and EN 60204-1 (PELV)
Noxious gas test ISA-S71.04-1985 G3 Harsh Group A
UL approvals UL/C-UL listed UL 508
UL/C-UL Recognized UL 60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
ATEX ? II 3 G Ex ec nC IIC T4 Gc
DEKRA 20ATEX0136 X
IECEx Ex ec nC IIC T4 Gc
DEK 20.0082X
Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC
Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU
EMC requirements for noise emission EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity EN 61000-6-1
EN 61000-6-2
Noise immunity EN 61000-6-2:2005
Electrostatic discharge
Standards/regulations EN 61000-4-2
Electrostatic discharge
Contact discharge 8 kV (Test Level 4)
Discharge in air 15 kV (Test Level 4)
Comments Criterion B
Electromagnetic HF field
Standards/regulations EN 61000-4-3
Electromagnetic HF field
Frequency range 80 MHz ... 1 GHz
Test field strength 20 V/m (Test Level 3)
Frequency range 1 GHz ... 2 GHz
Test field strength 10 V/m (Test Level 3)
Frequency range 2 GHz ... 3 GHz
Test field strength 10 V/m (Test Level 3)
Comments Criterion A
Fast transients (burst)
Standards/regulations EN 61000-4-4
Fast transients (burst)
Input 2 kV (Test Level 3 - asymmetrical)
Output 2 kV (Test Level 3 - asymmetrical)
Signal 2 kV (Test Level 4 - asymmetrical)
Comments Criterion B
Surge voltage load (surge)
Standards/regulations EN 61000-4-5
Input 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal 1 kV (Test Level 2 - asymmetrical)
Comments Criterion B
Conducted interference
Standards/regulations EN 61000-4-6
Conducted interference
I/O/S asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Comments Criterion A
Voltage 10 V (Test Level 3)
Emitted interference
Standards/regulations EN 61000-6-3
Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A Normal operating behavior within the specified limits.
Criterion B Temporary impairment to operational behavior that is corrected by the device itself
ECLASS-11.0 27371010
ECLASS-13.0 Redundanzmodul
ECLASS-13.0 Redundanzmodul
ECLASS-12.0 27371010
ETIM
ETIM 8.0 EC000683
UNSPSC
UNSPSC 21.0 32151500