2702524 – Phoenix Contact
STOCK: 0.00 unidade(s)
PSR-PS22-1NO-1NC-24VDC-SC Coupling Relay “Phoenix Contact”
Coupling relay for SIL 3 high and low-demand applications, couples digital output signals to the I/O, 1 enabling current path, 1 confirmation current path, safe state off applications, test pulse filter, fixed screw terminal block
Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.
Product type Coupling relay
Application Safe switch off
High demand
Low demand
Ex
Relay type Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Insulation characteristics
Overvoltage category III
Times
Typ. starting time with Us < 150 ms (with Us when controlled via A1)
Typical release time < 30 ms (when controlled via A1)
Recovery time 500 ms
Maximum power dissipation for nominal condition 3.28 W (IL² = 36 A²)
Nominal operating mode 100% operating factor
Rated insulation voltage 250 V AC
Rated surge voltage/insulation Basic insulation 4 kV between all current paths and housing
Safe isolation, 6 kV reinforced insulation from the control circuit (A1/A2) and diagnostics circuit (0V/21/22) to the enabling current path (13/14)
Supply
Rated control circuit supply voltage US 20.4 V DC ... 26.4 V DC
Rated control circuit supply voltage US 24 V DC -15 % / +10 % (A1/A2)
Rated control supply current IS typ. 45 mA
Power consumption at US typ. 1.08 W
Inrush current typ. 150 mA (?t < 5 ms at Us)
Filter time max. 3 ms (at A1-A2 in the event of voltage dips at Us)
max. 3 ms (at A1-A2; low test pulse width)
= 50 ms (at A1-A2; low test pulse rate)
max. 17 ms (at A1-A2; high test pulse width)
= 600 ms (at A1-A2; high test pulse rate)
Diagnostic supply voltage UD 24 V DC -15 % / +10 % (21/0V)
Input current at UD 6 mA (at the contacts 21/0V for UD; + 100 mA depending on load at contact 22)
Inrush current at UD typ. 200 mA (?t < 1 ms; for contacts 21 - 0 V at UD)
Protective circuit Serial protection against polarity reversal; 33 V suppressor diode (A1-A2)33 V suppressor diode (21/0V)
Relay: Enabling current path
Output description 2 N/O contacts in series, without delay, floating
Number of outputs 1 (safety-related N/O contacts: 13/14)
Contact type 1 enabling current path
Contact material AgSnO2
Switching voltage min. 12 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity min. 60 mW
Inrush current min. 3 mA
max. 6 A
Switching capacity according to IEC 60947-5-1 4 A (24 V (DC13))
5 A (250 V (AC15))
Limiting continuous current 6 A (High demand)
4 A (Low demand)
Sq. Total current 36 A2 (observe derating)
Switching frequency max. 1 Hz
Mechanical service life 10x 106 cycles
Output fuse 6 A gL/gG
4 A gL/gG (for low-demand applications)
Relay: Confirmation current path
Output description 2 N/C contacts in series, without delay, not floating (reference ground: A2)
Number of outputs 1 (safety-related N/C contacts: 21/22)
Contact type 1 confirmation current path
Contact material AgCuNi, + Au
Switching voltage min. 20.4 V DC
max. 26.4 V DC
Switching capacity min. 20 mW
Inrush current min. 1 mA
max. 100 mA
Limiting continuous current 100 mA
Switching frequency max. 1 Hz
Mechanical service life 10x 106 cycles
Output fuse 150 mA Fast-blow
Connection technology
pluggable no
Conductor connection
Connection method Screw connection
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG 24 ... 12
Stripping length 12 mm
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Status display 2 x green LEDs
Operating voltage display 1 x yellow LED
Error indication 1 x red LED
Width 6.8 mm
Height 93.1 mm
Depth 102.5 mm
Housing material PBT
Safety data
Stop category 0
Safety data: EN 50156-2
Safety Integrity Level (SIL) 3 (Reference IEC 61508)
Safety data: IEC 61508 - High demand
Designation Readback via N/C contact 22
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.996 %
MTBF 29.18 Years
?SU 2857.88 FIT
?SD 0 FIT
?DU 0.11 FIT
?DD 5.45 FIT
Probability of a hazardous failure per hour (PFHD) 1.00 x 10-9
Proof test interval 240 Months
Duration of use 240 Months
Designation Error acknowledgment via A1 to DO
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.961 %
MTBF 29.18 Years
?SU 2855.45 FIT
?SD 0 FIT
?DU 1.12 FIT
?DD 6.86 FIT
Probability of a hazardous failure per hour (PFHD) 1.56 x 10-9
Proof test interval 240 Months
Duration of use 240 Months
Safety data: IEC 61508 - Low demand
Designation Readback via N/C contact 22
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.839 %
MTBF 30.94 Years
?SU 2639.18 FIT
?SD 0 FIT
?DU 4.26 FIT
?DD 0 FIT
Probability of a hazardous failure on demand (PFDAVG) 1.36 x 10-4
1.87 x 10-5
Proof test interval 72 Months
Duration of use 240 Months
Designation Error acknowledgment via A1 to DO
Equipment type Type A
Safety Integrity Level (SIL) 3
Safe Failure Fraction (SFF) 99.907 %
MTBF 30.94 Years
?SU 2634.25 FIT
?SD 0 FIT
?DU 2.45 FIT
?DD 6.74 FIT
Probability of a hazardous failure on demand (PFDAVG) 1.48 x 10-4
7.08 x 10-5
Proof test interval 46 Months
Duration of use 240 Months
Ambient conditions
Degree of protection IP20
Min. degree of protection of inst. location IP54
Ambient temperature (operation) -40 °C ... 70 °C (observe derating)
Ambient temperature (storage/transport) -40 °C ... 85 °C
Maximum altitude = 2000 m (Above sea level)
Max. permissible humidity (storage/transport) 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation) 75 % (on average, 85% infrequently, non-condensing)
Shock 15g
Vibration (operation) 10 Hz ... 150 Hz, 2g
ATEX
Identification ? II 3 G Ex nA nC IIC T4 Gc
Certificate DEMKO 14 ATEX 1284X
IECEx
Identification Ex nA nC IIC T4 Gc
Certificate IECEx ULD 14.0003X
UL, USA / Canada
Identification cULus
Certificate E140324
UL, USA / Canada
Identification Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X
Class I, Div. 2, Groups A, B, C, D, T4
Certificate E360692
CE
Certificate CE-compliant
Air clearances and creepage distances between the power circuits
Standards/regulations EN 60664-1, EN 60079-15
Mounting type DIN rail mounting
Assembly instructions See derating curve
Mounting position vertical or horizontal
ECLASS
ECLASS-9.0 27371819
ECLASS-10.0.1 27371819
ECLASS-11.0 27371819
ETIM
ETIM 8.0 EC001449
UNSPSC
UNSPSC 21.0 39122200
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50 years
For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”