Autosimatic - Grupo Luminag

2866763 – Phoenix Contact

2866763 – Phoenix Contact

STOCK: 0.00 unidade(s)
QUINT-PS/1AC/24DC/10 Power supply 24VDC/10A “Phoenix Contact”

EAN: 4046356113793
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection. The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC … 56 V DC are covered
Nominal input voltage range 100 V AC … 240 V AC
110 V DC … 250 V DC
Input voltage range 85 V AC … 264 V AC
110 V DC … 350 V DC (typ. 90 V DC (UL 508: = 300 V DC))
Input voltage range AC 85 V AC … 264 V AC
Input voltage range DC 90 V DC … 350 V DC (UL 508: = 300 V DC)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC/DC
Inrush current < 15 A Inrush current integral (I2t) < 1.5 A2s AC frequency range 45 Hz ... 65 Hz Frequency range DC 0 Hz Mains buffering time > 36 ms (120 V AC)
> 36 ms (230 V AC)
Current consumption 2.2 A (120 V AC)
1.3 A (230 V AC)
2.5 A (110 V DC)
1.2 A (220 V DC)
Nominal power consumption 302 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.85
Typical response time < 0.15 s Input fuse 10 A (slow-blow, internal) Permissible backup fuse B10 B16 AC: Permissible DC backup fuse DC: Connect a suitable fuse upstream Recommended breaker for input protection 10 A ... 20 A (AC: Characteristics B, C, D, K) Discharge current to PE < 3.5 mA Efficiency > 92.5 % (for 230 V AC and nominal values)
Output characteristic U/I
Nominal output voltage 24 V DC ±1 %
Setting range of the output voltage (USet) 18 V DC … 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN) 10 A (-25 °C … 60 °C, UOUT = 24 V DC)
POWER BOOST (IBoost) 15 A (-25 °C … 40 °C permanent, UOUT = 24 V DC )
Selective Fuse Breaking (ISFB) 60 A (12 ms)
Magnetic circuit breaker tripping B2 / B4 / B6 / C2 / C4
Derating 60 °C … 70 °C (2.5%/K)
Feedback voltage resistance = 35 V DC
Protection against overvoltage at the output (OVP) = 35 V DC
Control deviation < 1 % (change in load, static 10 % ... 90 %) < 2 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Residual ripple < 50 mVPP (with nominal values) Short-circuit-proof yes Output power 240 W Maximum no-load power dissipation 9.1 W Power loss nominal load max. 22 W Rise time < 0.05 s (UOUT (10 % ... 90 %)) Connection in parallel yes, for redundancy and increased capacity Connection in series yes Signal: DC OK active Output description UOUT > 0.9 x UN: High signal
Switching voltage range 18 V DC … 24 V DC
Maximum inrush current = 20 mA (short-circuit-proof)
Continuous load current = 20 mA
Signal: DC OK floating
Output description Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage 30 V AC
24 V DC
Maximum inrush current 0.5 A
1 A
Continuous load current = 1 A
Signal: POWER BOOST, active
Output description IOUT < IN: High signal Switching voltage range 18 V DC ... 24 V DC Output voltage + 24 V DC Maximum inrush current 20 mA (short-circuit-proof) Continuous load current = 20 mA Connection method Screw connection Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 2.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 2.5 mm² Conductor cross section AWG min. 16 Conductor cross section AWG max. 12 Stripping length 7 mm Screw thread M3 Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Output Connection method Screw connection Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 2.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 2.5 mm² Conductor cross section AWG min. 16 Conductor cross section AWG max. 12 Stripping length 7 mm Screw thread M3 Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Signal Connection method Screw connection Conductor cross section solid min. 0.2 mm² Conductor cross section solid max. 2.5 mm² Conductor cross section flexible min. 0.2 mm² Conductor cross section flexible max. 2.5 mm² Conductor cross section AWG min. 16 Conductor cross section AWG max. 12 Screw thread M3 Tightening torque, min 0.5 Nm Tightening torque max 0.6 Nm Types of signaling LED Active switching output Relay contact Signal output: DC OK active Status display UOUT > 0.9 x UN: “DC OK” LED green
Note on status display UOUT < 0.9 x UN: Flashing "DC OK" LED IOUT < IN: LED ON Signal output: DC OK floating Status display UOUT > 0.9 x UN: “DC OK” LED green
Note on status display UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: POWER BOOST, active Status display IOUT > IN: LED “BOOST” yellow
Number of phases 1.00
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Product type Power supply
MTBF (IEC 61709, SN 29500) > 940000 h (25 °C)
> 530000 h (40 °C)
> 230000 h (60 °C)
Protection class I
Degree of pollution 2
Width 60 mm
Height 130 mm
Depth 125 mm
Installation distance right/left 5 mm / 5 mm
Installation distance top/bottom 50 mm / 50 mm
Alternative assembly
Width 122 mm
Height 130 mm
Depth 63 mm
Mounting type DIN rail mounting
Assembly instructions alignable: PN =50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom Mounting position horizontal DIN rail NS 35, EN 60715 With protective coating No Housing material Metal Hood version Galvanized sheet steel, free from chrome (VI) Side element version Aluminum Degree of protection IP20 Ambient temperature (operation) -25 °C ... 70 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport) -40 °C … 85 °C
Ambient temperature (start-up type tested) -40 °C
Maximum altitude 5000 m
Climatic class 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation) = 95 % (at 25 °C, non-condensing)
Shock 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation) < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min Rail applications EN 50121-4 EN 50121-3-2 HART FSK Physical Layer Test Specification Compliance Output voltage UOut compliant Standard – Limitation of mains harmonic currents EN 61000-3-2 Standard - Electrical safety IEC 61010-2-201 (SELV) Standard - Equipment safety BG (design tested) Standard - Approval for medical use IEC 60601-1, 2 x MOOP Standard – Safety extra-low voltage IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use IEC 61010-1 Approval - requirement of the semiconductor industry with regard to mains voltage dips SEMI F47-0706 Compliance Certificate DeviceNet approval DeviceNet™ Power Supply Conformance Tested Overvoltage category EN 62477-1 III CSA CAN/CSA-C22.2 No. 60950-1-07 CSA-C22.2 No. 107.1-01 Shipbuilding approval DNV GL (EMC B), ABS, LR, RINA, NK, BV SIQ BG (type approved) UL approvals UL Listed UL 508 UL/C-UL Recognized UL 60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) DeviceNet approval DeviceNet™ Power Supply Conformance Tested Low Voltage Directive Conformance with Low Voltage Directive 2014/35/EC Electromagnetic compatibility Conformance with EMC Directive 2014/30/EU EMC requirements for noise emission EN 61000-6-3 EN 61000-6-4 EMC requirements for noise immunity EN 61000-6-1 EN 61000-6-2 Noise immunity EN 61000-6-2 Electrostatic discharge Standards/regulations EN 61000-4-2 Electrostatic discharge Contact discharge 8 kV (Test Level 4) Discharge in air 15 kV (Test Level 4) Comments Criterion A Electromagnetic HF field Standards/regulations EN 61000-4-3 Electromagnetic HF field Frequency range 80 MHz ... 1 GHz Test field strength 20 V/m (Test Level 3) Frequency range 1 GHz ... 2 GHz Test field strength 10 V/m (Test Level 3) Frequency range 2 GHz ... 3 GHz Test field strength 10 V/m (Test Level 3) Comments Criterion A Fast transients (burst) Standards/regulations EN 61000-4-4 Fast transients (burst) Input 4 kV (Test Level 4 - asymmetrical) Output 2 kV (Test Level 3 - asymmetrical) Signal 2 kV (Test Level 4 - asymmetrical) Comments Criterion A Surge voltage load (surge) Standards/regulations EN 61000-4-5 Input 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal 1 kV (Test Level 2 - asymmetrical) Comments Criterion B Conducted interference Standards/regulations EN 61000-4-6 Conducted interference I/O/S asymmetrical Frequency range 0.15 MHz ... 80 MHz Comments Criterion A Voltage 10 V (Test Level 3) Emitted interference Standards/regulations EN 61000-6-3 Radio interference voltage in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Emitted radio interference in acc. with EN 55011 EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A Normal operating behavior within the specified limits. Criterion B Temporary impairment to operational behavior that is corrected by the device itself ECLASS-9.0 27040701 ECLASS-10.0.1 27040701 ECLASS-11.0 27040701 ETIM ETIM 8.0 EC002540 UNSPSC UNSPSC 21.0 39121000 REACh SVHC Lead 7439-92-1 China RoHS Environmentally Friendly Use Period = 25; For information on hazardous substances, refer to the manufacturer’s declaration available under “Downloads”

REF: 2866763 Categoria: