Autosimatic - Grupo Luminag

A9D37610 – Schneider

A9D37610 – Schneider

STOCK: 0.00 unidade(s)
RCBO 1P+N 10A C 10kA 30mA TypeA Acti9 iDPN H Vigi “Schneider”

This Acti9 iDPN Vigi is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 10A In rated current and C tripping curve. The earth leakage protection class is A type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icn rated short circuit breaking capacity is up to 10000A according EN/IEC 61009-2-1 standard. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. Its earth fault indicator on front face allows quick identification of the type of default. It can be fitted instead og a miniature circuit breaker for complete protection of one circuit. This product is compliant with EN/IEC 61009-2-1 standard. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 220VAC to 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is white (RAL9003). The dimensions are (W) 36mm x (H) 85mm x (D) 73mm. The weight is 125g. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -25°C to 60°C. The storage temperature is from -40°C to 85°C.

device application
Distribution
poles description
1P + N
number of protected poles
1
neutral position
Left
[In] rated current
10 A
network type
AC
trip unit technology
Thermal-magnetic
curve code
C
earth-leakage sensitivity
30 mA
earth-leakage protection time delay
Instantaneous
earth-leakage protection class
Type A
breaking capacity
10000 A Icn at 220…240 V AC 50 Hz conforming to EN/IEC 61009-2-1
suitability for isolation
Yes conforming to EN/IEC 60947-2
Complementary
device location in system
Outgoer
network frequency
50 Hz
[Ue] rated operational voltage
220…240 V AC 50 Hz
magnetic tripping limit
5…10 x In
residual current tripping technology
Voltage independent
[Ics] rated service breaking capacity
7500 A 75 % x Icn at 220…240 V AC 50 Hz conforming to EN/IEC 61009-2-1
rated breaking and making capacity
Idm 10000 A at 220…240 V AC 50 Hz conforming to EN/IEC 61009-2-1
limitation class
3 conforming to EN/IEC 61009-2-1
[Ui] rated insulation voltage
400 V AC 50 Hz
[Uimp] rated impulse withstand voltage
4 kV
contact position indicator
Yes
control type
Toggle
local signalling
ON, OFF, fault trip
mounting mode
Clip-on
mounting support
DIN rail
comb busbar and distribution block compatibility
Top or bottom: YES
connection pitch
9 mm between phase and neutral
9 mm pitches
4
Height
85 mm
width
36 mm
Depth
73 mm
Net weight
125 g
colour
White
mechanical durability
20000 cycles
electrical durability
20000 cycles
locking options description
Padlocking device
connections – terminals
Single terminal top or bottom 1…16 mm² rigid
Single terminal top or bottom 1…10 mm² flexible
Single terminal top or bottom 1…10 mm² flexible with ferrule
wire stripping length
15 mm for top or bottom connection
tightening torque
2 N.m top or bottom
earth-leakage protection
Integrated
Environment
standards
EN/IEC 61009-2-1
product certifications
VDE
IP degree of protection
IP20 conforming to IEC 60529
IP40 (modular enclosure) conforming to IEC 60529
pollution degree
3
overvoltage category
III conforming to IEC 60364
electromagnetic compatibility
8/20 µs impulse withstand, 250 A conforming to EN/IEC 61009-2-1
tropicalisation
2 conforming to IEC 60068-1
relative humidity
95 % at 55 °C
ambient air temperature for operation
-25…60 °C
Ambient air temperature for storage
-40…85 °C