Autosimatic - Grupo Luminag

A9F07325 – Schneider

A9F07325 – Schneider

STOCK: 0.00 unidade(s)
Miniature Circuit Breaker (MCB) Acti9 iC60H 3P 25A C 043867 curve 10000A (IEC 60898-1) 15kA (IEC 60947-2) double term.

This Acti9 iC60H is a multistandard low voltage miniature circuit breaker (MCB) with double tunnel terminals. It is a 3P circuit breaker with 3 protected poles, 25A rated current and C tripping curve. The rated short circuit breaking capacity goes up to 30kA at 220VAC to 240VAC conforming to EN/IEC 60947-2 standard and 10000A at 400VAC conforming to EN/IEC 60898-1 standard. It complies with both industrial standard EN/IEC 60898-1 and residential standard EN/IEC 60947-2. This miniature circuit breaker protects circuit against short circuit and overload current. Its unique VisiTrip indicator reduces intervention time by showing the faulty circuit. Its VisiSafe green strip guarantees the physical opening of the contacts to allow downstream maintenance. Its fast closing mechanism independent of manual operation improves its service life. It has an electrical endurance going up to 10000 cycles and a mechanical endurance going up to 20000 cycles. The Ui rated insulation voltage is 500VAC. Its limitation class 3 (according to EN/IEC60898-1) improves downstream circuit protection cost. The product can be clipped on a DIN rail. Its width is 6 pitches of 9mm. Pollution degree is 3. Overvoltage category is IV. The product colour is white (RAL9003). The dimensions are (W) 54mm x (H) 91mm x (D) 78.5mm. The weight is 0.375kg. It has an IP20 degree of protection (as per IEC/EN 60529) on its terminals. The operating temperature is -35°C to 70°C. The storage temperature is -40°C to 85°C
Device application
Distribution
Range
Acti9
Product name
Acti9 iC60
Product or component type
Miniature circuit-breaker
Device short name
iC60H
Poles description
3P
Number of protected poles
3
[In] rated current
25 A
Network type
AC
DC
Trip unit technology
Thermal-magnetic
Curve code
C
Breaking capacity
10000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1
42 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at 380…415 V AC 50/60 Hz conforming to EN/IEC 60947-2
30 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2
42 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2
15 kA Icu at <= 180 V DC conforming to EN/IEC 60947-2 Utilisation category Category A conforming to EN 60898-1 Category A conforming to IEC 60898-1 Suitability for isolation Yes conforming to EN 60898-1 Yes conforming to EN 60947-2 Yes conforming to IEC 60898-1 Yes conforming to IEC 60947-2 Standards EN 60947-2 IEC 60947-2 EN 60898-1 IEC 60898-1 Complementary Network frequency 50/60 Hz Magnetic tripping limit 8 x In +/- 20 % [Ics] rated service breaking capacity 15 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz 15 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz 5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz 7500 A 75 % conforming to EN 60898-1 - 400 V AC 50/60 Hz 7500 A 75 % conforming to IEC 60898-1 - 400 V AC 50/60 Hz 21 kA 50 % conforming to IEC 60947-2 - 12...133 V AC 50/60 Hz 21 kA 50 % conforming to EN 60947-2 - 12...133 V AC 50/60 Hz 15 kA 100 % conforming to IEC 60947-2 - 125...180 V DC 15 kA 100 % conforming to EN 60947-2 - 125...180 V DC Limitation class 3 conforming to EN 60898-1 3 conforming to IEC 60898-1 [Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2 500 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-2 6 kV conforming to IEC 60947-2 Contact position indicator Yes control type Toggle local signalling Trip indicator mounting support DIN rail 9 mm pitches 6 height 91 mm Width 54 mm Depth 78.5 mm Net weight 0.375 kg Colour White Mechanical durability 20000 cycles Electrical durability 10000 cycles Connections - terminals Double terminal (top or bottom) 1…25 mm² rigid Double terminal (top or bottom) 1…16 mm² flexible Wire stripping length 14 mm for top or bottom connection Tightening torque 2 N.m top or bottom earth-leakage protection Separate block Environment IP degree of protection IP20 conforming to IEC 60529 IP20 conforming to EN 60529 Pollution degree 3 Overvoltage category IV Tropicalisation 2 Relative humidity 95 % at 55 °C ambient air temperature for operation -35…70 °C Ambient air temperature for storage -40…85 °C Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Height 7.5 cm Package 1 Width 5.4 cm Package 1 Length 9.5 cm Package 1 Weight 360.0 g Unit Type of Package 2 BB1 Number of Units in Package 2 4 Package 2 Height 8.5 cm Package 2 Width 9.8 cm Package 2 Length 22.0 cm Package 2 Weight 1.512 kg Unit Type of Package 3 S03 Number of Units in Package 3 44 Package 3 Height 30.0 cm Package 3 Width 30.0 cm Package 3 Length 40.0 cm Package 3 Weight 17.049 kg

REF: A9F07325 Categoria: