Autosimatic - Grupo Luminag

ILX69-PBM – ProSoft Technology

ILX69-PBM – ProSoft Technology

STOCK: 0.00 unidade(s)
PROFIBUS DPV1 Master for CompactLogix “Rockwell Automation – ProSoft Technology”

The ILX69-PBM PROFIBUS DPV1 Master module provides all the advantages of in-chassis PROFIBUS communication, such as the inclusion of an AOI and the Autoscan features which greatly reduce your commissioning time, and ComDTM that provides remote Ethernet connectivity with asset management software.
With these modules, CompactLogix™ processors can easily communicate with slave devices supporting PROFIBUS DPV0 and DPV1 protocol. The module acts as an input/output module between the PROFIBUS network and the processor supporting complete Master specifications according to IEC 61158
Features and Benefits
AOI: Module communication is integrated within Studio/RSLogix 5000 using a sample Add-On Instruction (AOI), or sample ladder logic file, reducing commissioning time.
Autoscan: The new Autoscan feature reduces start up times and simplifies troubleshooting by scanning the PROFIBUS network and uploading slave device addresses and configuration information. (Reads and maps nodes automatically to the module.)
ComDTM: Allows remote Ethernet connectivity with Asset Management Software significantly lowering maintenance costs. You can configure, commission, maintain and diagnose your fieldbus devices throughout their entire lifecycle with this comprehensive, fully integrated engineering and maintenance environment.
SD card slot (SD card optional) is used for storing configuration files in the event of a disaster. It can also be used to update the firmware of the module without the need of a 1769 CPU
Slaves
Maximum 125
Input/Output
Maximum 244 Bytes per Slave
Input Data
Maximum 5712 Bytes
Acyclic Data
DPV1
Status data
88 Bytes
Output data
Maximum 5760 Bytes
DPV1 services
Class 1 Read/Write
Class 1 Alarm
Class 2 Initiate/Read/Write/Data transport/Abort
Services
Global-Control, Slave-Diagnostic, Set-Parameter
Sync, Freeze Command
Supported
Baud rate
9.6 kBaud,
19.2 kBaud,
45.45 kBaud,
93.75 kBaud,
187.5 kBaud,
500 kBaud,
1.5 MBaud,
3 MBaud,
6 MBaud,
12 MBaud
Auto-detection mode is supported
Hardware Specification
Specification
Description
PROFIBUS Interface
RS-485, max. 12 Mbps, potential free, according
EN 50170
Diagnostic Interface
10/100 Ethernet, RJ45
Power Supply
+5 V ±5 % / 570 mA
Max. Distance Rating
2 slots
Dimensions
Standard 1769 Single-slot module
Burst
EN 61000-4-4, 2 kV, 5 kHz
Surge
EN 61000-4-5, 2 kV common mode, 1 kV differential mode
ESD
EN 61000-4-2, 4 kV contact, 8 kV air, 4 kV indirect
Radiated/Conducted Immunity
EN 61000-4-3, 10 V/m, 30 …1000 MHz, 80% AM, 1 kHz sine wave
EN 61000-4-6, 10 V, 0,15 …30 MHz
Radiated/Conducted Emission
EN 55011 Class A
Vibration/Shock
IEC 600068-2-6, 10-150 Hz, ± 0,75 mm, ± 1 g, 1 Octave/min
IEC 600068-2-27, 15 g, 11 ms
Operating Temperature
0°C to 60°C (32°F to 140°F)
Relative Humidity
5 to 95% (non-condensing)
PROFIBUS conformance
Certified
ATEX Letter of Conformity 55.24 kB Last Modified 05/12/2022
CB Safety 388.14 kB Last Modified 02/26/2020
Declaration of Conformity (RoHS/CE) 442.33 kB Last Modified 12/18/2020
UL/CUL; Class1, Div. 2 388.14 kB Last Modified 02/14/2019
PI PROFIBUS Certification 158.38 kB Last Modified 09/15/2017
Country Approval – Eurasian Customs Union Conformity (EAC) (Wired) 1.92 MB Last Modified 02/11/2022
Korean KC Registration 261.73 kB Last Modified 03/25/2020
Declaration of REACH Compliance 341.08 kB Last Modified 02/08/2021

REF: ILX69-PBM Categoria: