Bus Terminal 2Channel Analog Input 0-10V 12bit “Beckhoff”
The KL3062 analog input terminal handles signals in the range from 0 to 10 V. The voltage is digitized to a resolution of 12 bits and is transmitted, electrically isolated, to the higher-level automation device. The input channels of the Bus Terminal have a common ground potential, the reference ground. The run LEDs give an indication of the data exchange with the Bus Coupler
Number of inputs 2
Power supply via the K-bus
Signal voltage 0…10 V
Technology single-ended
Internal resistance typ. > 200 kO
Common-mode voltage UCM –
Resolution 12 bit
Conversion time ~ 2 ms
Measurement error/ uncertainty < ±0.3 % (relative to full scale value)
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts – (no power contacts)
Current consumption K-bus typ. 60 mA
Bit width in the process image input: 2 x 16 bit data (2 x 8 bit control/status optional)
Configuration no address or configuration setting
Weight approx. 60 g
Operating/storage temperature 0…+55 °C/-25…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. rating/installation pos. IP20/variable
Pluggable wiring for all KSxxxx Bus Terminals
Approvals/markings CE, UL, ATEX
Ex marking II 3 G Ex nA IIC T4 Gc
Technical data
Housing data
To top
Housing data KL-12-8pin KS-12-8pin
Design form compact terminal housing with signal LEDs terminal housing with pluggable wiring level
Material polycarbonate
Dimensions (W x H x D) 12 mm x 100 mm x 68 mm
Installation on 35 mm DIN rail, conforming to EN 60715 with lock
Side by side mounting by means of double slot and key connection
Marking labeling of the BZxxx series
Wiring solid conductor (e), flexible conductor (f) and ferrule (a): spring actuation by screwdriver
Connection cross-section s*: 0.08…2.5 mm²,
st*: 0.08…2.5 mm²,
f*: 0.14…1.5 mm² s*: 0.08…1.5 mm²,
st*: 0.08…1.5 mm²,
f*: 0.14…1.5 mm²
Connection cross-section AWG s*: AWG 28…14,
st*: AWG 28…14,
f*: AWG 26…16 s*: AWG 28…16,
st*: AWG 28…16,
f*: AWG 26…16
Stripping length 8…9 mm 9…10 mm
Current load power contacts Imax: 10 A