Autosimatic - Grupo Luminag

X20BC00E3 – B&R Automation

X20BC00E3 – B&R Automation

STOCK: 0.00 unidade(s)
Bus Controller PROFINET IO Slave “B&R Automation”

B&R ID code 0xBB7D
Status indicators Module status, bus function
Diagnostics
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Power consumption
Bus 2.5 W
Additional power dissipation caused by actuators (resistive) [W] –
Certifications
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user’s manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
EAC Yes
Interfaces
Fieldbus PROFINET IO slave
PROFINET attributes
Conformance class B
Performance class RT
Variant 2x shielded RJ45 (switch)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex Yes
Autonegotiation Yes
Auto-MDI/MDIX Yes
Min. cycle time
Fieldbus 1 ms
X2X Link 250 µs
Synchronization between bus systems possible Yes
Electrical properties
Electrical isolation PROFINET isolated from bus and I/O
Operating conditions
Mounting orientation
Horizontal Yes
Vertical Yes
Installation elevation above sea level
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating –
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB80 separately.
Pitch 37.5+0.2mm

Fieldbus: PROFINET IO
I/O configuration via the fieldbus
Conformance Class B (RT)
Minimum cycle time 1 ms
Integrated switch for cabling multiple slaves
100 Mbit/s full duplex mode
Up to 1440 bytes of input data and up to 1440 bytes of output data are possible
Integrated website
PROFINET diagnostics and module diagnostics during runtime from within the master environment
Module and switch diagnostics during runtime using the website or SNMP
PROFINET (Process Field Network) is an Industrial Ethernet protocol. It uses TCP/IP and is real-time capable.

X20 modules or other modules based on X2X Link can be connected to the bus controller. Modular system configurations are optimally supported by PROFINET. Using the device description file (GSDML format), it is very easy to handle project configuration in the respective engineering tool from the manufacturer of the master device.

REF: X20BC00E3 Categoria: